LC1-F is used in AC 50Hz( or 60Hz ), rated working voltage is up to 660V, and rated current 115-630A under rated voltage 380V and category AC-3, for long-distance making and breaking circuit and frequently trip motor, can be conveniently added auxiliary contact arrangement or air time-delay terminal, and can interoperable with the appropriate thermal overload relay as electromagnetic starter for protecting potential overload circuit.

2, SPECIFICATIONS:

Type LC1-F115 LC1-F150 LC1-F185 LC1-F225 LC1-F265
Rated operation current(A) AC-1 115 150 185 225 265
AC-3 200 250 275 315 350
Standard power ratings of 3-phase motors AC-3(KW) 220V 30 40 55 63 75
380V 55 75 90 110 132
415V 59 80 100 110 140
440V 59 80 100 110 140
500V 75 90 110 129 160
660V/690V 80 100 110 129 160
1000V 65 65 100 100 147

 

Type LC1-F330 LC1-F400 LC1-F500 LC1-F630 LC1-F780
Rated operation current(A) AC-1 330 400 500 630 780
AC-3 400 500 700 1000 1600
Standard power ratings of 3-phase motors AC-3(KW) 220V/230V 100 110 147 200 220
380V/400V 160 200 250 335 400
415V 180 200 280 375 425
440V 200 250 295 400 425
500V 200 257 355 400 450
660V/690V 200 280 335 450 475
1000V 160 185 335 450 450